Technical Specifications

All of our cables are engineered to achieve greater levels of productivity and safety…and to last longer in the rigorous Australian mining & industrial environments.

Application
For mains, submains and subcircuits unenclosed, enclosed in conduit, buried direct or in underground ducts for buildings and industrial plants where subject to mechanical damage. Suitable for glanding.StandardAS/NZS 5000.1
Voltage600/1000V
ConductorCopper 2.5 - 120mm2
InsulationXLPE, X-90 Red, White, Blue & Green/Yellow
SheathPVC, 5V-90 Orange
Max Operating Temp90ºC

Request a Quote

Our team can consult on the best mix of products based on the scope of your project, site or machinery or we’ll happily quote to order. Fill out the form below or contact us on +61 8 9202 6816.

Send us mail

Technical Specifications

ConductorCurrent RatingElectrical Characteristics
Nominal Area mm2Unenclosed in AirBuried DirectBuried in DuctsMaximum DC Resistance @20ºC Ohms/kmMaximum DC Resistance @90ºC Ohms/kmEquivalent Star Reactance Ohms/km3 Phase Voltage Drop @90ºC mV/Am(b)
2.52629297.419.450.098816.4
43537374.615.880.09310.2
64546463.083.930.08876.8
106263631.832.330.0844.05
1683110811.151.470.08052.55
251111431070.7270.9270.08081.61
351371721300.5240.6690.07861.17
501682041550.3870.4940.07510.868
702132511930.2680.3430.07410.609
952633022330.1930.2480.07250.45
1203063442700.1530.1970.07130.366
(a) Based on 40°C ambient air temperature and where applicable, burial depth of 0.5m, soil temperature of 25°C and soil resistivity of 1.2°C.m/W.
(b) For single phase voltage drop, multiply by 1.155.
The above information is from the following sources:
AS/NZS 3008.1.1 (tables 14, 30, 35, 42)
AS 1125 (table 2.3) For current ratings with other installation conditions refer to AS/NZS 3008.1.1.
Do not put in direct contact with polystyrene, polyurethane or similar thermal insulation materials
ConductorCurrent RatingElectrical Characteristics
Nominal Area mm2Unenclosed in AirBuried DirectBuried in DuctsMaximum DC Resistance @20ºC Ohms/kmMaximum DC Resistance @90ºC Ohms/kmEquivalent Star Reactance Ohms/km3 Phase Voltage Drop @90ºC mV/Am(b)
2.52629297.419.450.098816.4
43537374.615.880.09310.2
64546463.083.930.08876.8
106263631.832.330.0844.05
1683110811.151.470.08052.55
251111431070.7270.9270.08081.61
351371721300.5240.6690.07861.17
501682041550.3870.4940.07510.868
702132511930.2680.3430.07410.609
952633022330.1930.2480.07250.45
1203063442700.1530.1970.07130.366
(a) Based on 40°C ambient air temperature and where applicable, burial depth of 0.5m, soil temperature of 25°C and soil resistivity of 1.2°C.m/W.
(b) For single phase voltage drop, multiply by 1.155.
The above information is from the following sources:
AS/NZS 3008.1.1 (tables 14, 30, 35, 42)
AS 1125 (table 2.3) For current ratings with other installation conditions refer to AS/NZS 3008.1.1.
Do not put in direct contact with polystyrene, polyurethane or similar thermal insulation materials
Active/ConductorEarthDiameter under ArmourArmour Wire
Nominal Area mm2NUMBER & DIAMETER OF WIRES No/mmNOMINAL DIAMETER mmMINIMUM INSULATION THICKNESS mmNOMINAL AREA. mm2NUMBER & DIAMETER OF WIRES No/mmMINIMUM INSULATION THICKNESS mmmmNOMINAL DIAMETER mm
2.57/0.673.40.72.57/0.670.610.90.9
47/0.853.90.72.57/0.670.611.60.9
67/1.044.50.72.57/0.670.613.11.25
107/1.355.30.747/0.850.7151.25
167/1.706.30.767/1.040.717.51.25
257/2.146.40.967/1.040.722.21.6
357 strands70.9107/1.350.723.51.6
5019 strands8.11167/1.700.726.71.6
7019 strands9.81.1257/2.140.931.72
9519 strands11.41.1257/2.140.925.62
12019 strands12.91.2357 strands0.939.92